Skip to content

New name, same team: airfilterseurope.com is now valorfilters.com. Our products, prices and advice stay the same. Please update your bookmarks. Our e-mail address is now info@valorfilters.com.

When to replace your air filters

Monitor pressure drop, inspect your filters and know the maximum periods, so you replace them at the right time.

A clogged filter restricts the air and increases energy consumption. A filter changed too early is an unnecessary cost. So how do you know when to replace it? The main criterion is pressure drop. Regular visual inspection completes it.

The main criterion: pressure drop

Pressure drop (or differential pressure) is the difference in pressure between the upstream and downstream sides of the filter. It rises over time, as the filter holds more dust. According to Camfil, the best way to identify the right time to change a prefilter is to monitor its pressure drop. TROX also recommends differential pressure as the preferred criterion for replacement.

The differential pressure gauge

According to AFPRO, the filter section should be fitted with an indicator-type differential pressure gauge (not a liquid manometer) and an operating hours counter. Note the reading when the filter is new: this is the initial pressure drop. Then read it at regular intervals.

The final value

Each manufacturer states a recommended final pressure drop on its data sheet. Values differ from one product to another

  • TROX, PFG glass fibre bag filters: 250 to 350 Pa
  • TROX, PFC synthetic bag filters (coarse dust): 200 Pa
  • Lindab, bag filters: 450 Pa, except 250 Pa for classes G3, G4 and M5.

So use the value for the filter actually installed. The EN 13053:2019 standard, cited by Camfil, also offers a rule based on the initial value. Replacement is recommended when the pressure drop reaches

  • for an ISO Coarse filter: the initial value + 50 Pa, or 3 times the initial value
  • for an ISO ePM filter: the initial value + 100 Pa, or 3 times the initial value.

Whichever is lower applies. Example: an ISO ePM filter reading 100 Pa when new should be changed at 200 Pa (100 + 100), because 3 × 100 = 300 Pa is higher. Camfil uses this rule as the maximum final pressure drop for its Hi-Flo range.

Do not exceed the final value. According to Camfil, high pressure drop means high energy cost. A filter used for too long may also be damaged or even collapse, and contaminate the rest of the system.

Visual inspection

The gauge does not tell you everything: look at the filters too. According to AFPRO, the filter section should be easy to reach for visual inspection and replacement, and an airtight seal is essential. The model inspection plan from BGN (a German statutory accident insurance body) for simple supply air systems in commercial kitchens calls for a check every 3 months for

  • soiling
  • damage and leaks
  • odours.

If there is a problem, the affected filters or seals are replaced.

Replacement intervals

There is no universal lifetime. According to Camfil, a filter’s lifetime depends on local conditions: the same filter, at the same airflow, will last a longer or shorter time depending on the outdoor environment.

Some rules do set maximum periods, however. In Germany, the VDI 6022 hygiene guideline (Part 1) requires, according to the summary published by seventhings, that the first filter stage be replaced after 12 months at the latest, and later stages after 24 months at the latest; HEPA filters follow differential pressure and the manufacturer’s specifications. BGN’s model plan uses the same 12- and 24-month periods. These are upper limits, not targets: if the final value is reached sooner, the filter must be changed sooner. Check which rules apply to your installation.

In short

  1. Note the pressure drop of the new filter.
  2. Read the gauge regularly.
  3. Change the filter at the final value recommended by the manufacturer, or sooner if there is damage or a leak.
  4. Respect the maximum periods that apply to your installation.

To order replacement filters, add them to your quote list, or send us a photo of the label using the “Send a photo” form.

Sources